Label the windings by their role
The primary winding receives AC from the source. The secondary winding delivers energy to the load. A changing magnetic flux links the windings, and each turn that shares that flux has the same induced voltage in the ideal model. That is why voltage is proportional to turns. Each winding’s voltage and turn count must stay together when you set up the ratio.
Use p for primary and s for secondary. Write Vs ÷ Vp = Ns ÷ Np, where V denotes RMS voltage and N denotes turns. Both fractions put the secondary on top. If the secondary has half as many turns as the primary, it also has half the primary voltage. The direction of change is worth predicting before touching your calculator.
Isolate what the question leaves blank
To find the secondary voltage, multiply the primary voltage by the secondary-to-primary turns ratio. To find secondary turns, multiply primary turns by the secondary-to-primary voltage ratio. For a missing primary value, invert the corresponding ratio. The transformer ratio calculator lets you choose any of these four targets. The turn ratio is dimensionless, so multiplying volts by the ratio still gives volts.
A result like 157.5 turns can be a valid algebraic answer for an exact target voltage. A whole-turn winding would produce a different voltage. If a practice problem supplies a rounding rule, apply it at the end, then use the chosen integer turn count to calculate the resulting voltage if asked. Keep intermediate values unrounded so a rounded ratio does not change the winding count.
Calculate current from the load
Voltage follows the turn ratio. Under load, current follows its inverse in the ideal model. The input and output apparent powers match for the single-phase ideal transformer, Vp × Ip = Vs × Is, using RMS values. For example, with a voltage ratio of one-half and a secondary current of 8 A, the primary current is 4 A. The primary operates at twice the secondary voltage in that example, so the two VA products match.
If the exercise gives the apparent power in VA, divide by the voltage of the winding whose current you need. If it gives kVA, multiply by 1,000 first. If it gives real power in watts for a load whose power factor is below one, convert the watts to VA using the stated power factor before dividing by voltage.
A voltage ratio determines an ideal unloaded secondary voltage with only the primary voltage and both turn counts. To calculate load current, you also need a load, current or power value. In an actual transformer, losses and winding impedance can change the voltage under load. Exam prompts that assume ideal behavior let you work directly from the ratios.
Try a question
An ideal single-phase transformer has 600 turns on its 240 V RMS primary and 300 turns on the secondary. A load draws 600 VA at the secondary. Find the secondary voltage and both winding currents.
Show the answer
120 V RMS secondary, 5 A secondary and 2.5 A primary.
The secondary has half the turns, so its voltage is 240 × (300 ÷ 600) = 120 V. Divide the 600 VA by 120 V to get 5 A secondary. Divide the same 600 VA by 240 V to get 2.5 A primary. Check both sides by multiplying each winding’s voltage by its own current.